The elementary purpose of RST type switchgears is to equip pole transformer stations with transformers up to 630 kVA with the function to supply rural, urban and industrial service customers. The switchgear enables energy distribution to objects using an overhead or cable nN network. Switchgears of EMITER production are used successfully and find their place in all distribution and industrial companies.
Construction:
- aluminum sheet 2mm thick, shaped by punching and bending method,
- painting with polyester powder paint in RAL 7035,
- joining sheet elements by means of riveting and welding,
- the roof of the enclosure is equipped with a chimney, enabling the introduction of the power cable, the discharge of the drainage cables to the top, to the overhead line and street lighting,
- the bottom of the casing can be equipped with a flat plate or a board with chimneys enabling the introduction of drainage cables to the ground,
- the housing can also be equipped with a cable duct, protecting the drainage cables to the ground,
- the door has a 3-point locking system. There is the possibility of additional security with a padlock,
- the housing has two mounting channels in the middle, fastened with a crossbar. On request, it is possible to provide mounting brackets and mounting plates for the measuring field and other equipment elements,
- the mounting plate of the measuring field is opened on hinges,
- the door from the measuring field is equipped with a foldable laptop shelf.
Additional switchgear equipment:
- laptop shelf mounted on the door from the side of the measuring system,
- folding roof by the measuring system,
- service socket,
- bottom covers,
- it is possible to make a description on the switchgear door
- cable duct for the introduction of cable circuits.,
- pole holder,
- platform for the housing.
|

|

see in the catalog
|
Basic parameters:
Rated voltage |
400V/500V
|
The rated voltage of the insulation |
690V
|
Nominal frequency |
50Hz
|
Rated impulse withstand voltage |
12kV
|
The maximum current rating |
1250A
|
The rated current of the receiving circuits |
630A
|
Rated short-time withstand current |
20kA
|
Rated peak current withstand |
40kA
|
Change of drainage ducts |
50-240mm2
|
Level of security |
IP44, IK10
|
Insulation class |
I
|
Compatibility |
PN-EN 61439-1:2011 PN-EN 61439-2:2011 PN-EN 61439-5:2015-02 PN-EN 60529:2003 PN-EN 62262:2003 PN-E 05163:2002 PN-EN 61140:2005/A1:2008 PN-EN ISO 12944-2:2001P PN-EN ISO 1461:2001P
|
|